Details
Single phase Line Reactor 200C300E6/E1 introduces specific amount of inductive reactance (impedance) into a circuit. This inserted impedance reduces line harmonics, moderate line transients, holds down spikes of current, limit peak current, absorb power line disturbances which could damage inverters, variable speed controllers or other voltage sensitive equipment.
Line Reactor 200C300E6/E1 Winding Schematic:
Preliminary General Drawing. (Dimensions in inches).
*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.
Full Specification
Catalog No. | 200C300E6/E1 |
---|---|
Product Type | Line Reactor |
Phase | Single |
Maximum Current | 300 Amps |
Voltage range | 350 Volt |
Reactor Power Rate | No |
Frequency, Hz | 60 |
Inductance, mH | 0.30 |
Impedance | No |
Current over load capability | 150% for 1 min |
Saturation Level | 250% of rated current (50% rated inductance minimum at 350% rated current). |
Vector Group | II |
Winding Conductor | Copper |
Temperature Rise, °C | 115 |
Insulation Class | 180 (H) |
Insulation Level, (B.I.L), kVA | 4 |
Sound Level, dB | 70 |
Standards and Certifications | CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type) CSA certified. File No. LR34493 , UL Listed. File No.E108255. ISO9001 Quality Certification. |
Enclosure Type | Nema 1. General purpose indoor ventilated steel enclosure suitable for dry locations |
Weight, Lbs | 80.0 |
Country of Manufacture | Canada |