Buy, Order, Customize Dry type Electrical Transformers made in Canada online.
Saturday, December 21, 2024
Log In

Log In

Forgot Your Password?

Cart Subtotal: US$ 0.00

10 kVA 600 Volt to 115/230 Volt Single phase Epoxy Encapsulated Transformer SC10J-K1/EP

Be the first to review this product

Availability: NOT in stock. Current lead time to manufacture: 3 weeks

US$ 3,842.00
OR

Quick Overview

Catalog No.: SC10J-K1/EP
Epoxy Encapsulated Transformer 10 kVA • Single Phase • Primary: 600 Volt • Secondary: 115/230 Volt
Conductor: Copper. • Frequency 60 Hz.
+US$ 860.00
US$ 3,842.00

Details

Single phase Epoxy Encapsulated Transformer SC10J-K1/EP is an isolation transformer with primary and secondary windings that are physically separated from each other. It allows AC power to be taken from one device and fed into another without electrically connecting the two circuits. The transformer blocks transmission of DC currents but allow AC signals to pass. It is sealed in silica sand and resin solid mass, completely enclosing and protecting the core and coil, while significantly reducing audible noise and suitable for hazardous environments.

 Epoxy Encapsulated Transformer general dimensions

Preliminary General Drawing. (Dimension, inch).

*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.

Epoxy Encapsulated Transformer SC10J-K1/EP Winding Schematics:

 

II Single phase connection

Full Specification

Catalog No. SC10J-K1/EP
Product Type Epoxy Encapsulated Transformer
Phase Single
Power Rating 10 kVA
Frequency, Hz 60
Vector Group II
Primary voltage 600 Volt
Primary Max Current, Amps 16.7A
Primary Terminals H1-H2
Primary Terminal Lugs 2-14 AWG
Primary Voltage Taps 0%; ±2.5%; ±5.0%
Secondary Voltage 115/230 Volt
Secondary Max Current, Amps 87.0A at 115 Volt or 43.5A at 230 Volt
Secondary Terminals X1-X4, Interconnect for Lower Voltage: X1 to X3 and X2 to X4, or for Higher Voltage: X2 to X3
Secondary Terminal Lugs 2-14 AWG
Winding Conductor Copper
Temperature Rise, °C 130
Insulation Class 200 (N)
Insulation Level, (B.I.L), kVA 10
Efficiency at 35% Load, % 92.96
ANSI/IEEE Impedance, % 2.5-3.5
Sound Level, dB 40
Standards, Certifications, Compliances: CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)., CSA certified. File No. LR34493
Seismic Qualified SDS=1.60g 2/h=1.0 OSHPD OSP-0109-10 for USA zone 4 and Canada zone 6.
UL Listed. File No.E108255., Meets NEMA ST-20, ISO9001 Quality Certification.
Enclosure Type Nema 3R. Outdoor Non-Ventilated Weather resistant steel enclosure (IP54)
Weight, Lbs 230.0
Country of Manufacture Canada

You may also be interested in the following product(s)

 

Transformer Calculator

Help: To calculate required kVA of the transformer enter Load Amps, Load Volt and press "Required kVA" button. Also you can calculate Current from other two parameters.
Note: Recommended add up to 20% to the calculated kVA