Details
Single phase Autotransformer MC100J-C has common primary-secondary windings which are not insulated from each other, offers no interference or disturbance isolation between primary and secondary circuits. It is an economical solution but is not suitable for sensitive equipment with electronic components and perfectly suitable for simple motor or heater single applications.
Preliminary General Drawing. (Dimension, inch).
*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.
Autotransformer MC100J-C Winding Schematics:
Full Specification
Catalog No. | MC100J-C |
---|---|
Product Type | Autotransformer |
Phase | Single |
Power Rating | 100 kVA |
Frequency, Hz | 60 |
Vector Group | II |
Primary voltage | 600 Volt |
Primary Max Current, Amps | 166.7A |
Primary Terminals | H0-H1, 6-300MCM |
Secondary Voltage | 240 Volt |
Secondary Max Current, Amps | 416.7A |
Secondary Terminals | X0-X1, 2 of 300MCM |
Winding Conductor | Copper |
Temperature Rise, °C | 150 |
Insulation Class | 220 (R) |
Insulation Level, (B.I.L), kVA | 10 |
Efficiency at 35% Load, % | 97.5 |
ANSI/IEEE Impedance, % | 4.0-5.0 |
Sound Level, dB | 40 |
Standards, Certifications, Compliances: | CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)., CSA certified. File No. LR34493 Seismic Qualified SDS=1.60g 2/h=1.0 OSHPD OSP-0109-10 for USA zone 4 and Canada zone 6. UL Listed. File No.E108255., IEEE C57.12.01., IEEE C57.12.91, ISO9001 Quality Certification. |
Enclosure Type | Nema 3R. Outdoor ventilated Weather resistant steel enclosure (IP14). FINISH - Polyester powder coat. |
Weight, Lbs | 440.0 |
Country of Manufacture | Canada |