Buy, Order, Customize Dry type Electrical Transformers made in Canada online.
Monday, November 25, 2024
Log In

Log In

Forgot Your Password?

Cart Subtotal: US$ 0.00

100 kVA 460 Volt to 110/220 Volt Single phase Isolation Transformer SC100H1-K2/Z3

Be the first to review this product

Availability: NOT in stock. Current lead time to manufacture: 5-6 weeks

US$ 8,741.00
OR

Quick Overview

Catalog No.: SC100H1-K2/Z3
Isolation Transformer 100 kVA • Single Phase • Primary: 460 Volt • Secondary: 110/220 Volt
Conductor: Copper. • Frequency 60 Hz.
+US$ 860.00
US$ 8,741.00

Details

Single phase Isolation Transformer SC100H1-K2/Z3 has primary and secondary windings that are physically separated from each other. It allows AC power to be taken from one device and fed into another without electrically connecting the two circuits. The transformer blocks transmission of DC currents from one circuit to the other, but allow AC signals to pass, and also blocks interference caused by ground loops.

 Isolation Transformer general dimensions

Preliminary General Drawing. (Dimension, inch).

*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.

Isolation Transformer SC100H1-K2/Z3 Winding Schematics:

 

II Single phase connection

Full Specification

Catalog No. SC100H1-K2/Z3
Product Type Isolation Transformer
Phase Single
Power Rating 100 kVA
Frequency, Hz 60
Vector Group II
Primary voltage 460 Volt
Primary Max Current, Amps 217.4A
Primary Terminals H1-H2
Primary Terminal Lugs No
Primary Voltage Taps 0%; ±2.5%; ±5.0%
Secondary Voltage 110/220 Volt
Secondary Max Current, Amps 909.1A at 110 Volt or 454.5A at 220 Volt
Secondary Terminals X1-X4, Interconnect for Lower Voltage: X1 to X3 and X2 to X4, or for Higher Voltage: X2 to X3
Secondary Terminal Lugs No
Winding Conductor Copper
Temperature Rise, °C 150
Insulation Class 220 (R)
Insulation Level, (B.I.L), kVA 10
Efficiency at 35% Load, % 98.90
ANSI/IEEE Impedance, % 3.5-4.5
Sound Level, dB 50
Standards, Certifications, Compliances: Efficiency compliance: CANADA: SOR/DORS/2018-201 (NRCan 2019). CSA: CSA C802.2-18.,
USA: DOE 10 CFR PART 431:2016-01 (DOE 2016)., CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)., CSA certified. File No. LR34493
Seismic Qualified SDS=1.60g 2/h=1.0 OSHPD OSP-0109-10 for USA zone 4 and Canada zone 6.
UL Listed. File No.E108255., ISO9001 Quality Certification.
Enclosure Type Nema 3R. General purpose indoor ventilated steel enclosure suitable for dry locations. Sprinkler Proof when angle between sprinkler and opening does not exceed 45° (IP14). FINISH - Polyester powder coat.
Weight, Lbs 820.0
Country of Manufacture Canada

You may also be interested in the following product(s)

 

Transformer Calculator

Help: To calculate required kVA of the transformer enter Load Amps, Load Volt and press "Required kVA" button. Also you can calculate Current from other two parameters.
Note: Recommended add up to 20% to the calculated kVA