Details
Three phase Isolation Transformer BC75H1-M/Z3 has primary and secondary windings that are physically separated from each other. It allows AC power to be taken from one device and fed into another without electrically connecting the two circuits. The transformer blocks transmission of DC currents from one circuit to the other, but allow AC signals to pass, and also blocks interference caused by ground loops. Secondary neutral to ground bonding eliminates common mode noise, providing an isolated neutral-ground reference for sensitive equipment.
Preliminary General Drawing. (Dimension, inch).
*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.
Isolation Transformer BC75H1-M/Z3 Winding Schematics:
Full Specification
Catalog No. | BC75H1-M/Z3 |
---|---|
Product Type | Isolation Transformer |
Phase | Three |
Power Rating | 75 kVA |
Frequency, Hz | 60 |
Vector Group | Delta-Wye(DYn) |
Primary voltage | 460 Volt |
Primary Max Current, Amps | 94.1A |
Primary Terminals | H1-H2-H3 |
Primary Terminal Lugs | 2/0-6 AWG |
Primary Voltage Taps | 0%; ±2.5%; ±5.0% |
Secondary Voltage | 208Y/120 Volt |
Secondary Max Current, Amps | 208.2A |
Secondary Terminals | X0-X1-X2-X3 |
Secondary Terminal Lugs | 6-300MCM |
Winding Conductor | Copper |
Temperature Rise, °C | 150 |
Insulation Class | 220 (R) |
Insulation Level, (B.I.L), kVA | 10 |
Efficiency at 35% Load, % | 98.62 |
ANSI/IEEE Impedance, % | 4.5-5.5 |
Sound Level, dB | 50 |
Standards, Certifications, Compliances: | Efficiency compliance: CANADA: SOR/DORS/2018-201 (NRCan 2019). CSA: CSA C802.2-18., USA: DOE 10 CFR PART 431:2016-01 (DOE 2016)., CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)., CSA certified. File No. LR34493 Seismic Qualified SDS=1.60g 2/h=1.0 OSHPD OSP-0109-10 for USA zone 4 and Canada zone 6. UL Listed. File No.E108255., ISO9001 Quality Certification. |
Enclosure Type | Nema 3R. General purpose indoor ventilated steel enclosure suitable for dry locations. Sprinkler Proof when angle between sprinkler and opening does not exceed 45° (IP14). FINISH - Polyester powder coat. |
Weight, Lbs | 740.0 |
Country of Manufacture | Canada |